Power factor calculator

Enter two known values to get the rest, then add a target power factor to size a capacitor bank.

About Power Factor Calculator

Power factor tells you how much of the current your load draws is doing useful work. Real power in kW, apparent power in kVA and reactive power in kVAR form a right triangle, and the power factor is the ratio of kW to kVA. Choose which two values you know, optionally give a voltage to see the line current, and a target power factor to get the capacitor size that closes the gap. Single phase and three phase supplies are both covered.

  • Sizing a capacitor bank for a motor load.
  • Seeing how much current correction would save.
  • Converting between kW, kVA and kVAR.
  • Checking a utility bill that penalises a low power factor.

How to use Power Factor Calculator

1

Step 1

Choose which two values you know and type them.

2

Step 2

Pick single or three phase, and add the voltage if you want the current.

3

Step 3

Type a target power factor to get the capacitor kVAR.

Good to know

  • Example: 100 kW at a power factor of 0.8 is 125 kVA and 75 kVAR. Raising it to 0.95 needs about 42.1 kVAR of capacitors.
  • The calculation treats the load as inductive, which is the usual case for motors. A leading load needs a different approach.
  • The result is a planning estimate. Harmonics, switching and capacitor ratings matter in real installations, so ask a qualified electrician to design and fit correction.

Common questions

What is a good power factor?

Closer to 1 is better. Many utilities ask for 0.9 or 0.95 and may charge extra below that, but the limit depends on your supplier.

How is the capacitor size worked out?

Qc = kW x (tan of the old angle - tan of the new angle). The angle is the arc cosine of the power factor.

Does the phase matter?

Not for kW, kVA, kVAR and power factor, which hold for both. It matters for the current, which is kVA x 1000 / V for single phase and kVA x 1000 / (1.732 x V) for three phase.